Safety Approvals

European Hazardous
Location Approval

The 1794-IRT8, 1794-IRT8K, and 1794-IRT8XT modules are European
Hazardous Location approved.

European Zone 2 Certification (The following applies when the product bears the
Ex or EEx Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by

European Union Directive 94/9/EC and has been found to comply with the Essential Health

and Safety Requirements relating to the design and construction of Category 3 equipment

intended for use in potentially explosive atmospheres, given in Annex II to this Directive.

Compliance with the Essential Health and Safety Requirements has been assured by

compliance with EN 60079-15 and EN 60079-0.

WARNING

Observe the following additional Zone 2 certification requirements.

• This equipment is not resistant to sunlight or other sources of UV

radiation.

• This equipment must be installed in an enclosure providing at

least IP54 protection when applied in Zone 2 environments.

• This equipment shall be used within its specified ratings defined

by Allen-Bradley.

• Provision shall be made to prevent the rated voltage from being

exceeded by transient disturbances of more than 40% when
applied in Zone 2 environments.

• Secure any external connections that mate to this equipment by

using screws, sliding latches, threaded connectors, or other
means provided with this product.

• Do not disconnect equipment unless power has been removed or

the area is known to be nonhazardous.