Data Transfer File Instructions

Chapter 11

11-2

Figure 11.1

Types of Counter Indexing

DM

WordĆtoĆFile Move

Counter Addr:

Position:

FIle Length:

Word Addr:

File R:

001

007

110

500Ć 506

200

200

15

DM

FileĆtoĆWord Move

Counter Addr:

Position:

FIle Length:

Word Addr:

File A:

001

007

110

400Ć 406

200

200

15

EN

FileĆtoĆFile Move

Counter Addr:

Position:

FIle Length:

File R:

File A:

001

007

500Ć 506

400Ć 406

200

200

17

Rate Per Scan

007

DM

200

15

externally indexed

file instructions

internally indexed

file instructions

Externally Indexed

An externally indexed counter must be controlled by other rungs of your
program. The counter address is used to identify the file instruction. The
counter address holds the accumulated value. The accumulated value of
the counter points to the file’s position value. The position value is the
accumulated value and it represents the specific word location within the
file. The preset value of the counter represents the length of the file.

Another characteristic of the externally indexed file instruction is that it
only has a done bit. This is bit 15. The done bit is automatically entered
from the counter address. It is set when the operation is complete and
remains set as long as the rung condition is true.

Internally Indexed

Internally indexed means that the counter is internally incremented by the
instruction itself. No outside control is required. You assign an address to
the counter.

In Figure 11.1 notice that a value for rate per scan is needed. The rate per
scan defines the number of words which are operated upon during one
scan. For example, suppose you have a file that contains twelve words. If
you assign the value of 004 for the rate per scan that means that the
instruction executes four words per scan at a time. Therefore, the entire
operation is completed in three consecutive scans.