Sequencers

Chapter 12

12-14

Insert the following values. The cursor moves automatically throughout
the instruction. The values are:

COUNTER ADDR: 200
CURRENT STEP: 001
SEQ LENGTH: 006
WORDS PER STEP: 1
FILE: 600
MASK: 075
OUTPUT WORDS:
1:012 2: 013

The sequencer output instruction should look like this:

EN

Sequencer Output

Counter Addr:

Current Step:

Seq Length:

200

001

006

DN

Words Per Step:

File:

Mask:

2

600Ć 613

075Ć 076

200

17

200

15

Output Words

1: 012

3: 4:

200

001

006

2

400Ć 413

070Ć 071

1: 110

3: 4:

Sequencer Input

Counter Addr:

Current Step:

Seq Length:

Words Per Step:

File:

Mask:
Input Words

2. 201 2. 013

For this example, enter data using the binary data monitor mode. Get your
data from the worksheet (Figure 12.5). A filled block means that a 1
should be inserted in the corresponding bit location.