Chapter

12

12-1

Sequencers

This describes the three types of sequence instructions:

sequencer

input

sequencer

output

sequencer

load

These instructions either transfer information from the data table to output
word addresses, compare I/O word information with information stored in
tables, or transfer I/O word information into the data table.

Sequencer instructions can transfer information from the data table to
output word addresses for the control of sequential machine operation
(sequencer output); compare I/O word information stored in tables so that
machine operation conditions can be examined for control and diagnostic
purposes (sequencer input); and transfer I/O word information into the
sequencer file (sequencer load).

File instructions operate on files that are one word or 16 bits wide. In
contrast, sequencer instructions operate on files that are up to four words or
64 bits wide. A sequencer file can be represented graphically by a
sequencer table. The length or number of steps (rows) in a sequencer table
can be up to 999. The width of a sequencer table can be up to four words
(columns) as shown in Figure 12.1.

Figure 12.1

Sequencer Table

Step

Word 1

Word 2

Word 3

Word 4

001

002

003

"

"

"

"

"

"

024

00110101 11000101

00011101 11001010

10111011 11001011

01011101 01011111

01110100 00011101

00010111 00110011

01010101 01010101

00010101 10100000

10100010 10101000

01010000 01011111

10111100 00110011

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

"

Chapter Objectives

Comparison with File

Instructions

Advertising