Data Transfer File Instructions

Chapter 11

11-16

Notice that file R’s POSITION has not changed.

Now practice by changing POSITION 006 of file A to 7777.

Important: If you want to change the data in FILE R, you follow the same

procedure. To move your cursor to file R press the [SHIFT}, [

].

Purpose: Duplicates and transfers the data of a word from the data table to
a specified word within a file.

Programmed as an output instruction; requires four words of the user
program area. Your program must externally index the counter.

When the rung goes:

True - Data from a designated word address in the data table is transferred
to the selected position in the source file.

False - No action is taken.

Keystrokes: You enter a word to file move by performing the
following steps.

[FILE]

11

The screen does not change.

WordĆToĆFile Move

Counter Addr:

Position:

File Length:

30

001

001

DN

Word Addr:

File R:

010

110-110

030

15

0

Parameters: The procedure for entering the parameters for a word to file
move is the same as the procedure for a file to file move.

Purpose: Duplicates and transfers the data of a word within your source
file to a specified word elsewhere in the data table.

Programmed as an output instruction; requires four words of the user
program area. Your program must externally index the counter.

Word to File Move

File to Word Move

Advertising