Block Transfer

Chapter 14

14-5

Here is an explanation of each value:

This Value:

Stores the:

Data Address

First possible address in the timer/counter accumulated value area

of the data table

Module Address

RGS for R = rack, G = module, S = slot number

Block Length

Number of words to be transferred
(enter 00 for default value or for 64 words)

File

Address of the first word of the file

Enable bit Ć(EN)Ć

Automatically entered from the module address
Set on when the rung containing the instruction is true

Done bit Ć(DN)Ć

Automatically entered from the module address
Remains on for 1 program scan following successful transfer

Data Address

The data address stores the module address of the block transfer module.
The data address must be assigned the first available address in the
timer/counter accumulated area of the data table. This depends on the
number of I/O racks being used (Table 14.B). When more than one block
transfer module is used, consecutive data addresses must be assigned ahead
of address for timer and counter instructions.

Table 14.B

The First Available Address in

Timer/Counter Area of Data Table

# I/O Racks

First Available

Address

in Timer/

Counter Area

1

020

2

030

3

040

4

050

5

060

6

070

7

200

The last consecutive word in the accumulated area following the words
reserved for block transfer data addresses should be loaded with zeroes.
When the processor sees this boundary word, it does not search further for
block transfer data. In addition, the processor is prevented from finding
other BCD values that could, by chance, be in the same configuration as
the rack, group and slot numbers found in block transfer data addresses.