Rockwell Automation 1772-LS_LSP,D17726.8.6 PROG/OPER MANUAL-MINI PLC-2/05 User Manual

Page 166

Advertising
background image

Block Transfer

Chapter 14

14-11

Keystrokes: In this example, you enter a block transfer write instruction.

[BLOCK

XFER]

The screen does not change

EN

Block Xfer Write

Data Addr:
Module Addr:
Block Length:
File:

030
100

01

110

DN

010

06

110

06

110Ć

0

Note that the words BLOCK TRANSFER WRITE are flashing.

Insert the following values. The cursor moves automatically through
the instruction. The values are:

DATA ADDRESS 041
MODULE ADDRESS 130
BLOCK LENGTH 05
FILE 060-064

The instruction should look like this:

EN

Block Xfer Write

Data Addr:
Module Addr:
Block Length:
File:

041
130

05

064

DN

013

06

113

06

060Ć

Purpose: Bidirectional block transfer is the sequential performance of both
operations. The order of operation is generally determined by the module.

Two rungs of user program are required, one containing the block transfer
read instruction, the other containing the block transfer write instruction.
When both instructions are given the same module address, the pair are
considered as bidirectional block transfer instructions. Figure 14.6 shows
an example rung containing a bidirectional block transfer instruction and
the data table areas used by the instruction.

Bidirectional Block Transfer

Advertising