Chapter 8

8Ć7

The Up Counter instruction retains its AC value when:

You change the mode to the remote program.
The rung condition turns false.
A power outage occurs and memory backup is maintained.

Important: Bit 14 of the accumulated value word is set when the accumulated
value either overflows or underflows. when a down counter preset is 000, the
underflow bit 14 will not be set when the count goes below 0.

Down Counter

Purpose: The Down Counter instruction subtracts one from its accumulated
value for each false to true transition of its rung conditions. A count is only
added on a false to true transition, so rung conditions must go from true to false
and back to true before the next count is registered.

010

00

CTD

030

PR 150

AC 000

When the rung condition becomes:

True

Accumulated value decrements by 1.
Bit 14 is set when AC < 000.
Bit 15 is reset when AC < PR; counting continues.
Bit 16 is set and stays set until the rung goes false.

False

Accumulated value is retained.
Bit 14 - no action is taken.
Bit 15 - no action is taken.
Bit 16 is reset.

Counter Reset

Purpose: The Counter Reset instruction resets the up counter down counter
instructions accumulated value and status bits to 0.

010

00

CTR

030

PR 150

AC 000