Data Transfer File Instructions

Chapter 11

11-9

Purpose: Duplicates and transfers the source file to the destination file
address you identified. The source file remains intact.

Programmed as an output instruction; requires five words of the user
program area. The counter is incremented internally by the instruction.

ATTENTION: The counter address for the file-to-file move
instruction should be reserved for that instruction. Do not
manipulate the counter accumulated or preset word. Changes to
these values could result in unpredictable machine operation or
a run-time error. Damage to equipment and/or injury to
personnel could occur.

When the rung becomes:

True - The data is transferred from the source file to your designated file at
the specified rate per scan.

False - no action is taken.

Keystrokes: You enter a file to file move by performing the
following steps.

[FILE]

10

The screen does not change.

EN

FileĆToĆFile Move

Counter Addr:

Position:

File Length:

30

001

001

DN

File A:

File R:

Rate Per Scan:

110-110

110-110

001

030

17

030

15

0

Parameters: Notice that the cursor is now on the first digit of the counter
address. Also, the display shows all default values.

File to File Move