Scan Theory

Chapter 5

5Ć5

Instruction Name

Instruction

False

Instruction

True

Symbol

Label

LBL

34

Ć

Return Ć(RET)Ć

30

15

Jump to subroutine Ć(JSR)Ć

100

15

Jump Ć(JMP)Ć

55

15

Block transfer read BLOCK

XĆFER 1

80

75

Block transfer write BLOCK

XĆFER 0

80

75

Sequencer load SEQ 2

390(80/extra word)

105

Sequencer input SEQ 1

420(90/extra word)

55

Sequencer output SEQ 0

470(90/extra word)

110

FileĆtoĆword move FILE 12

250

45

WordĆtoĆfile move FILE 11

250

45

FileĆtoĆfile move FILE 10440 (+10/word

transferred)

200

1

When a rung that contains a ZCL instruction is false, the execution time of each instruction between the start fence and

end fence is 17 microseconds per word.

Here is an explanation of the rungs in Figure 5.2:

Rung 1 - The count increments its accumulated value each time this rung
is true.

Rung 2 - This rung enables the counter to increment on the next scan. If we did
not have this rung, the counter would always be true and it would not
increment. Remember: Counters increment only on false to true transitions.

Rung 3 - The timer times in tenths of seconds when we are counting. This
value is displayed on the industrial terminal screen.

Rung 4 - The average scan time is displayed beneath store 2 and store 3
in milliseconds.

Important: Refer to three digit math in chapter 10.

Rung 5 - The counter overflow bit is re-setting the timer.

Rung 6 - The counter overflow bit is resetting the counter.

We described scan sequence and a method to measure average scan time. The
next chapter explains some of the instructions you use in a program.