Rockwell Automation 1772-LS_LSP,D17726.8.6 PROG/OPER MANUAL-MINI PLC-2/05 User Manual

Page 264

Advertising
background image

Quick Reference

Appendix C

CĆ8

Table C.G

Timer Instructions

NOTE: The timer word address, XXX, is assigned to the timer accumulated areas of the data table. To determine which addresses are

valid accumulated areas, the most significant digit in the word address must be an even number.
The time base, TB, is userĆselectable and can be 1.0, 0.1, or 0.01 second. Preset values, YYY, and accumulated values, ZZZ, can vary

from 000 to 999.
Bit 15 is the timed bit. Bit 17 is the enable bit.
The word address displayed will be 3 or 4 digits long depending on the data table size. When entering the word address, use a leading

zero if necessary.

Key Symbol

Instruction Name

1770-T3 Display

Rung Conditions

Status Bits

-(TON)-

Timer On Delay

XXX

-(TON)-

TB

PR YYY

AC ZZZ

When the rung is true, the timer

begins to increment the

accumulated value at a rate

specified by the time base.
When the rung is false, the timer

reset the accumulated value

to 000.

When the rung is true:

bit 15-set when AC=PR

bit 17-set
When the rung is false:

bits 15 and 17-reset

-(TOF)-

Timer Off Delay

XXX

-(TOF)-

TB

PR YYY

AC ZZZ

When the rung is true, the timer

resets the accumulated value

at 000.
When the rung is false, the timer

begins to increment the

accumulated value.

When the rung is true:

bit 15-set bit 17-set.
When the rung is false:

bit 15-resets when AC=PR

bit 17-reset

-(RTO)-

Retentive Timer

-(RTO)-

TB

PR YYY

AC ZZZ

When the rung is true, the timer

begins to increment the

accumulated value. When false,

the accumulated value is retained.

When the rung is true:

bit 15-set when AC=PR

bit 17-set
When the rung is false:

bit 15-no action is taken

bit 17-reset

-(RTR)-

Retentive Timer Reset

XXX

-(RTR)-

PR YYY

AC ZZZ

XXX - Word address of the

retentive timer it is resetting.
The preset and accumulated

values are automatically entered by

the industrial terminal.
When the rung is true, the

accumulated value and status bits

are reset.

When the rung is true:

bit 15 and 17-reset
When the rung is false: no action is

taken