Scan Theory

Chapter 5

5Ć4

Add the execution values for each instruction by using Table 5.A. The sum of

these values added to the I/O scan time is the average scan time.

Table 5.A

Approximate Execution Time Per Scan (in average microseconds)

Instruction Name

Symbol

Instruction

True

Instruction

False

Examine on, Examine off

Ć| |Ć,Ć| / |Ć

14

11

Output energize

Ć( )Ć

16

16

Output latch

Ć(L)Ć

17

13

Output unlatch

Ć(U)Ć

17

13

Get

Ć[G]Ć

28

Ć

Put

Ć(PUT)Ć

26

14

Equal

Ć(=)Ć

23

11

Less than

Ć(<)Ć

25

13

Get byte

Ć|B|Ć

16

Ć

Limit test

Ć|L|Ć

24

11

Counter reset

Ć(CTR)Ć

20

14

Retentive timer reset

Ć(RTR)Ć

20

14

Timer onĆdelay

Ć(TON)Ć

75

47

Retentive timer onĆdelay

Ć(RTO)Ć

78

48

Timer offĆdelay

Ć(TOF)Ć

82

60

Up counter

Ć(CTU)Ć

70

55

Down counter

Ć(CTD)Ć

75

60

3 Digit Math

Add

Ć(+)Ć

48

15

Subtract

Ć(Ć)Ć

80

19

Multiply

Ć(x)Ć(x)Ć

615

60

Divide

Ć(

÷

)Ć(

÷

875

60

Add to any of the above when its

address is 4008 or greater

27

27

Expanded Math

Add

EAF 01

400Ć500

40

Subtract

EAF 02

400Ć500

40

Multiply

EAF 03

800Ć2250

40

Divide

EAF 04

500Ć3250

40

Square root

EAF 05

1850

40

BCD to binary

EAF 13

500

40

Binary to BCD

EAF 14

500

40

Master control reset

Ć(MCR)Ć

16

16

Zone control last state

1

Ć(ZCL)Ć

22(no skip)

20+(13 per word skipped)

Branch start

16

16

Branch end

18

18

End, temporary end

T.END

27

27

Subroutine area

SBR

27

27

Immediate input update

Ć[ I ]Ć

45 (with forcing on 55)

Ć

Immediate output update

Ć(IOT)Ć

70(with forcing on 80)

17