Equipment Installation
4-5
7712-IN001B-EN-P – June 2013
Disengage cart latch
Figure 4.6 – Contactor Cart Latch
Grab handle, keeping key engaged, and fi rmly remove contractor cart from
enclosure onto the service cart.
Figure 4.7 – Contactor Cart Removal Handle
A clear space of 1300 mm is required in front of the
equipment to facilitate removal of the contactor cart is
required.
I M P O R T A N T
I M P O R T A N T
This method of removing the contactor cart is only
valid if the equipment is installed on a level fl oor. If the
equipment is installed on an elevated platform, alternate
means are required. Consult factory for details.