4-20 Equipment

Installation

7712-IN001B-EN-P – June 2013

4.9

Ground Bus Linking

Figure 4.30 – Ground Bus Links at the Front of the Cabinet

Slide bus links between sections in the slot. Secure the ground bus link
together with the adjoining section. Secure to 37 ft-lb/51 N·m.

S H O C K H A Z A R D

S H O C K H A Z A R D

The ground bus links must be properly secured to ensure

the entire MV MCC line up is properly grounded.