OneGear™ Standard Plenum Assembly Procedure

5-3

7712-IN001B-EN-P – June 2013

Figure 5.3 – Gasket location

7. Locate the mounting holes on top of the OneGear™ unit to mount the

front and rear assembly (shown in Figure 5.4).

Mounting Holes (Rear)

Mounting Holes (Front)

Figure 5.4 – Mounting location for plenum

8. Take the rear plate (81021-070-01/02) of 7712/7719 plenum assembly,

position it as shown in Figure 5.5a, and connect it to the adapter plate
and OneGear top plate using the rear inner bracket (81021-961-51) and
M8 hardware (M8 HHCS, 28 mm [1.125"] OD fl at washers and lock
washer).