Equipment Installation

4-19

7712-IN001B-EN-P – June 2013

4.8 Connecting

to

Load

Terminals

Figure 4.29 – Load Terminals at the Front of the Cabinet

With the starter in the fi nal location, and the load cables are now inside the
starter, connect the load cables to the load terminals of the starter. Secure
to 75 ft-lbs/102 N·m.

S H O C K H A Z A R D

S H O C K H A Z A R D

Load cables must be securely attached to the starter load

terminals to reduce the impact of electrical arc at this
location.

Load Terminals U, V, X