Che c k lis t-2, Control signal terminal block connections, Ac input power connections – Rockwell Automation VSM500 Integrated Drive/Motor User Manual

Page 10

Advertising
background image

Che

c

k

lis

t-2

In

s

talling and

Operati

n

g the V

S

M

500 Int

egr

at

ed
Drive/Motor, V

e

rsion

3.

0

3>Important: To stop the unit using the terminal

1> The jumper between terminals 7 and 11
must be removed when wiring the
Function Loss input. See section 7.1 for
more information.

2> An external 0 to 10 volt or 4 to 20 mA
speed reference source can be connected.
See section 7.5.3 for more information.

2>

2> Parameter Settings from Setup Switches

1> Start from Operator Controls

input.

device such as PLC

Connect to external

1 10 Volt Reference

4 Common
5 0 to 10V Output

2 0 to 10V Spd Ref Input
3 4 to 20 mA Spd Ref Input

16 Start
17 Stop

7 24V DC

13 24V DC

8 Speed Preset 2
9 Speed Preset 1

10 Speed Preset 0
11 Function Loss

12 RPM / %Load Display

14 Forward/Reverse
15 Reset

18 24 DC Common
19 N.O. Relay

20 Relay Common

6 Common

6 Common

Reverse Disabled (Reverse Lockout)

Ramp-to-Rest Stop

Constant Torque Curve

Auto Restart Enabled

Relay Output Control: Faulted

Power-Up Start Enabled

1 = 1800 RPM (60 Hz) (Default)

2 = 2100 RPM (70 Hz)
3 = 2400 RPM (80 Hz)

4 = 2700 RPM (90 Hz)
5 = 3000 RPM (100 Hz)

6 = 3300 RPM (110 Hz)
7 = 3600 RPM (120 Hz)

0 = 1500 RPM (50 Hz)

input.

device such as PLC

Connect to external

2> Switch 10 is used only with the DeviceNet Communication Option board.

1> Switches 2 and 9 are used only with local operator control units.

Connector

7 = 90 sec

6 = 60 sec

5 = 30 sec

4 = 20 sec

3 = 15 sec

2 = 10 sec

1 = 5 sec (Default)

0 = 1 sec accel / 5 sec decel

(Stop to Max Spd)

Standard Unit

Local Operator Control Unit

+ -

%LOAD

RPM

1>

Parameter Settings from EEPROM Memory

Start from Terminal Block

Auto Restart Disabled

Variable Torque Curve

Power-Up Start Disabled

Relay Output Control: Running

1> Spd Ref from Operator Controls

Analog Spd Ref from Terminal Block

Coast-to-Rest Stop

Reverse Enabled

0 Hz Minimum Speed

Min Spd from Terminal Block Inputs

Start

Momentary 3-Wire

Ground

1 10 Volt Reference

+10VDC

3 4 to 20 mA Spd Ref Input

2 0 to 10V Spd Ref Input

4 Common

8 Speed Preset 2

1>

7 24V DC

5 0 to 10V Output

9 Speed Preset 1

5K

2>

FWD

+ -

REV

13

RPM

%LOAD

16
17

Start

Maintained 2-Wire

= N.C. Momentary Contact

= Maintained Contact - Closed

= Maintained Contact - Open

= N.O. Momentary Contact

Control Signal Terminal Block Connections

20 Relay Common

19 N.O. Relay

18 24 DC Common

17 Stop

16 Start

15 Reset

14 Forward/Reverse

13 24V DC

11 Function Loss

10 Speed Preset 0

12 RPM / %Load Display

AC Inputs

DC Bus (Do Not Wire)

AC Input Power
Connections

- DBR (Do Not Wire)

Display Board

With Cover Removed

Top View of Unit

Setup Slide Switch

Max Speed Switch

Accel / Decel Switch

3>

3>

6

0

7

2

1

5

4

3

7

0

1

5

4

3

2

6

10

9

O

1

N

23

5

4

7

68

= Default Setting (OFF Position)

block inputs, the jumper between terminals 13 and
17 must be removed when wiring the Stop input. See
section 7.6 for more information.