Installing and Operating the VSM500 Integrated Drive/Motor, Version 3.0
7.8
Wiring Reset Control
Important: This applies only to standard units and local operator control units set up
for terminal block control (setup slide switch position 9 = ON, see section
8.3.9).
An open-to-closed transition at the Reset input (control terminal 15) clears a fault once
the appropriate corrective action has been taken. After clearing the fault, you must
reassert the Start command in order to restart the unit.
Wire a normally-open (N.O.) pushbutton between control terminals 15 and 13 as
shown in figure 7.14. Refer to chapter 11, Diagnostics and Troubleshooting, for more
information on faults.
Figure 7.14 – Reset Control Wiring
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Reset
24V DC
= N.O. Momentary Contact