8 wiring reset control – Rockwell Automation VSM500 Integrated Drive/Motor User Manual

Page 44

Advertising
background image

7-14

Installing and Operating the VSM500 Integrated Drive/Motor, Version 3.0

7.8

Wiring Reset Control

Important: This applies only to standard units and local operator control units set up

for terminal block control (setup slide switch position 9 = ON, see section
8.3.9).

An open-to-closed transition at the Reset input (control terminal 15) clears a fault once
the appropriate corrective action has been taken. After clearing the fault, you must
reassert the Start command in order to restart the unit.

Wire a normally-open (N.O.) pushbutton between control terminals 15 and 13 as
shown in figure 7.14. Refer to chapter 11, Diagnostics and Troubleshooting, for more
information on faults.

Figure 7.14 – Reset Control Wiring

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Reset

24V DC

= N.O. Momentary Contact

20