Observe the following precautions when troubleshooting the unit:

Stop the unit using either the Stop input or Function Loss input.

Disconnect, tag, and lockout AC power before working on the unit.

Verify that there is no voltage present at AC input terminals R/L1, S/L2, and T/L3.
Refer to figure 5.2 for the location of the terminals.

Wait five minutes and verify that the DC bus has discharged to zero volts. See figure
5.2 for the location of the DC bus test points.

11.1 Fault Codes and Corrective Actions

The following table describes normal operational faults that may be corrected by the
user. For standard units, the corrective action assumes that a Reset pushbutton is
wired between control terminals 15 and 13, as described in section 7.8.

If a fault occurs, do the following:

Step 1. Try to clear the fault first by pressing the Reset pushbutton (or

key on

local operator control units). If the fault reoccurs, continue with step 2.

Step 2. Refer to table 11.1 to identify the fault code and the possible causes.

Important: Contact Reliance if the displayed fault code is not in table 11.1.

Step 3. Perform the corrective action(s).

Step 4. Clear the fault by pressing the Reset pushbutton (or

key).

RESET

RESET

Table 11.1 – Fault Codes and Corrective Actions

Fault

Code

Fault Description

Fault Cause

Corrective Action

Communication Loss

Communication cable between
the DeviceNet option board and
the drive disconnected or
opened.

Turn off power to the unit. Verify
the cable connection between
the Regulator board and the
DeviceNet option board. Turn
power on to the unit.

Parameter Checksum

Contents of the EEPROM is
corrupted.

Reset parameters to default
values and cycle power.

or

Keypad Cable
Disconnected

Keypad cable disconnected
while unit under power.

Turn off power to the unit. Verify
the keypad cable connection.
Turn power on to the unit.

X

DeviceNet Communication
Fault where X = E, F, L, P,
or U.

Refer to the VSM500 DeviceNet
Option Board manual, D2-3463.

Keypad Cable Connected

Keypad cable connected while
unit under power.

Turn off power to the unit. Verify
the keypad cable connection.
Turn power on to the unit.