Step 8 - Verify the Setup and Adjust Switches if Required

8-11

8.3.9 Start Mode Select (Position 9)

Important: This switch applies only to the local operator control units.

The switch at position 9 is used to select whether the unit is controlled from the
operator controls or from the terminal block.

Note that if the unit is set up for terminal block control (Start Mode Select = ON), the

and

keys remains active.

Settings (Position 9)

OFF position = Control from the Operator Controls (default)
ON position = Control from the Terminal Block

Important: The drive will not start when power is applied after changing this setting.

The start command must be reasserted in order to start the drive.

8.3.10 Parameter Mode for DeviceNet Option (Position 10)

Important: This switch applies only to the DeviceNet Communication option.

The switch at position 10 is used to select whether the unit gets its parameter settings
from the rotary switches and setup slide switch (SW1, SW2, and SW3) or from the
EEPROM memory. Refer to the DeviceNet Option board instruction manual (D2-3463)
for information on installing and configuring the DeviceNet Option board.

This switch setting is read when power is applied.

Settings (Position 10)

OFF position = Parameter Settings from the Rotary Switches and Setup Slide

Switches (SW1, SW2, and SW3).

ON position = Parameter Settings from the EEPROM Memory.

RESET