Installing and Operating the VSM500 Integrated Drive/Motor, Version 3.0
When the switch in position 8 is ON, the minimum speed will be determined as shown
in the following table:
Control Terminal Block
Slide Switch Position 8 = ON
Terminal 8
Status
Terminal 9
Status
Terminal 10
Status
Minimum Speed Setting
Open
Open
Open
0 RPM (0 Hz)
Open
Open
Closed
150 RPM (5 Hz)
Open
Closed
Open
300 RPM (10 Hz)
Open
Closed
Closed
600 RPM (20 Hz)
Closed
Open
Open
900 RPM (30 Hz)
Closed
Open
Closed
1200 RPM (40 Hz)
Closed
Closed
Open
1500 RPM (50 Hz)
Closed
Closed
Closed
1800 RPM (60 Hz)
Figure 8.6 – Wiring Minimum Speed
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Min Speed 0
Min Speed 1
Min Speed 2
24V DC