Step 7 - Wire the Control Signal Terminal Block

7-7

7.4

Wiring RPM or %Load Display

The RPM or %Load Display input (control terminal 12) selects the type of information
displayed by the analog output and the built-in display, speed in RPM or %load. Wire a
switch between control terminals 12 and 13 as shown in figure 7.7.

7.5

Wiring the Speed Reference

The standard VSM500 unit provides two motor speed reference options:

Seven preset speeds

An external 0 to 10 VDC or 4 to 20 mA speed reference source

The VSM500 unit with local operator controls provides three motor speed
reference options:

The local operator controls (using the

keys)

Seven preset speeds (the

keys are not used)

An external 0 to 10 VDC or 4 to 20 mA speed reference source (the

keys

are not used)

Select the option that is the most suitable for your application. The following sections
provide wiring information for each option except the local operator controls. Refer to
section 1.2 for information on the local operator controls.

Figure 7.7 – RPM or %Load Display Wiring

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

RPM or %Load Display

24V DC

RPM

%Load