Hapter, Step 4 - install external components, 1 installing an ac input disconnect – Rockwell Automation VSM500 Integrated Drive/Motor User Manual

Page 23: 2 installing branch circuit protection

Advertising
background image

Step 4 - Install External Components

4-1

C

HAPTER

4

Step 4 - Install External Components

Install external components using the guidelines in the following sections.

4.1

Installing an AC Input Disconnect

An AC input disconnect must be provided in the incoming power lines in accordance
with NEC/CEC guidelines.

4.2

Installing Branch Circuit Protection

Install the required, user-supplied branch circuit protection fuses according to
NEC/CEC guidelines. Refer to table 4.1 for recommended fuse ratings.

!

ATTENTION: The NEC and CEC require that an input disconnect be
provided in the incoming power lines. Failure to observe this precaution
could result in severe bodily injury or loss of life.

!

ATTENTION: The NEC/CEC requires that upstream branch protection
be provided to protect input power wiring. The input fuse ratings listed
in table 4.1 are applicable for one VSM500 unit per branch circuit. No
other load can be applied to that fused branch circuit. Failure to observe
this precaution could result in severe bodily injury or loss of life.

Table 4.1 – Required AC Branch Circuit Protection

NEC Amps Input

Model Number

Input Voltage

Unit HP

Input

Current

Fuse

Rating

1

1

Recommended fuse type: UL Class J or CC, 600 V, time delay.

1_X_4_1_

460 VAC

1 HP

2.3 A

3.5 A

2_X_4_1_

460 VAC

2 HP

3.7 A

6.0 A

3_X_4_1_

460 VAC

3 HP

5.7 A

9.0 A

5_X_4_1_

460 VAC

5 HP

9.0 A

15.0 A

1_X_2_1_

230 VAC

1 HP

4.5 A

7.0 A

2_X_2_1_

230 VAC

2 HP

7.6 A

12.0 A

1_X_3_1_

230 VAC (1-Phase)

1 HP

5.8 A

9.0 A

2_X_3_1_

230 VAC (1-Phase)

2 HP

14.0 A

20.0 A

1_X_1_1_

115 VAC

1 HP

14.0 A

20.0 A