8-8

Installing and Operating the VSM500 Integrated Drive/Motor, Version 3.0

Settings (Position 4):

OFF position = Auto-Restart Disabled (Default)
ON position = Auto-Restart Enabled

8.3.5 Torque Curve (Position 5)

The switch at position 5 selects either a variable torque curve or a constant torque
curve. The variable torque selection provides a squared V/Hz curve and 110%
electronic thermal overload and 110% current limit for one minute. The constant
torque selection provides a linear V/Hz curve and 150% electronic thermal overload
and 150% current limit for one minute.

Settings (Position 5):

OFF position = Variable Torque Curve (Default)
ON position = Constant Torque Curve

Table 8.1 – Auto Restartable Faults

Fault Code

Description

Overcurrent

Overload

High bus voltage

Low bus voltage

Overtemperature

Figure 8.5 – Torque Curves

Base

Frequency

CT

VT

Hz

Output

Voltage

460 V