Step 8 - Verify the Setup and Adjust Switches if Required

8-5

Step 3. Apply AC input power.

Step 4. Set the desired operating speed.

Standard units: Use the speed potentiometer or other user-supplied
external speed reference device.

Local operator control units: Use the

key to increase the speed

reference and the

key to decrease the speed reference.

Step 5. Repeat the adjustment procedure until the desired acceleration / deceleration

time is obtained. Note that changes to the acceleration / deceleration time
are recognized only while the drive is stopped.

Important: If speed is erratic or not as expected, verify that only one of the speed reference

inputs (0 to 10 VDC or 4 to mA) has been wired.

8.3

Modifying the Setup Using the Setup Slide Switch

The switches in the 10-position setup slide switch define the characteristics of the
VSM500 unit as shown in figure 8.4. The switches are preset at the factory to suit a
wide range of applications and normally do not need to be changed. The following
sections describe how to modify the setup to suit your specific application, if required.

Important: Changes to the slide switch settings are recognized only while the drive is

stopped.

Figure 8.4 – Setup Slide Switch Selections

Minimum Speed From Terminal Block Inputs

Reverse Disabled (Reverse Lockout)

Ramp-to-Rest Stop

0 Hz Minimum Speed

Reverse Enabled

Coast-to-Rest Stop

8

67

Analog Speed Reference From Terminal Block

Constant Torque Curve

Auto Restart Enabled

Power-Up Start Enabled

Relay Control Output: Faulted

1> Speed Reference From Operator Controls

Relay Control Output: Running

Power-Up Start Disabled

Variable Torque Curve

Auto Restart Disabled

45

3

2

N

1

O

91

0

Start from Terminal Block

Parameter Settings from EEPROM Memory

= Default Setting (OFF position)

1> Switches 2 and 9 apply to local operator control units only.

1> Start from Operator Controls

2> Parameter Settings from Setup Switches

2> Switch 10 is used with the DeviceNet Communication option only.