Rockwell Automation VSM500 Integrated Drive/Motor User Manual

Page 38

Advertising
background image

7-8

Installing and Operating the VSM500 Integrated Drive/Motor, Version 3.0

7.5.1 Wiring the Preset Speed Inputs

Control terminals 8, 9, and 10 select seven preset speeds as shown in table 7.1. Note
that if you select a preset speed that is greater than the maximum speed setting
(based on the rotary switch setting), the unit uses the maximum speed setting value.

Important: Slide switch position 8 defines whether terminals 8, 9, and 10 are used as

presets (default) or to define the unit’s minimum speed (user option).
Refer to section 8.3.8 for information about using terminals 8, 9, and 10 to
select minimum speed.

To use the preset speeds to set the speed reference, wire to terminals 8, 9, and 10 as
shown in figure 7.8.

Table 7.1 – Fixed Preset Speed Selections

Selected Speed Reference

Terminal 8

Status

Terminal 9

Status

Terminal 10

Status

Standard Unit

Local Operator

Control Unit

Open

Open

Open

Analog speed reference

Local operator control

Open

Open

Closed

Preset 1 - 300 RPM (10 Hz)

Open

Closed

Open

Preset 2 - 600 RPM (20 Hz)

Open

Closed

Closed

Preset 3 - 900 RPM (30 Hz)

Closed

Open

Open

Preset 4 - 1200 RPM (40 Hz)

Closed

Open

Closed

Preset 5 - 1500 RPM (50 Hz)

Closed

Closed

Open

Preset 6 - 1800 RPM (60 Hz)

Closed

Closed

Closed

Preset 7 - 2100 RPM (70 Hz)

Figure 7.8 – Preset Speed Input Wiring

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Speed Preset 0

Speed Preset 1

Speed Preset 2

24V DC

= Maintained Contact - Open