Rockwell Automation VSM500 Integrated Drive/Motor User Manual

Page 46

Advertising
background image

8-2

Installing and Operating the VSM500 Integrated Drive/Motor, Version 3.0

Figure 8.1 – Factory Settings for the Setup Rotary Switches and Slide Switch

2

6

3

4

5

1

0

7

0 = 1500 RPM (50 Hz)
1 = 1800 RPM (60 Hz) (Default)
2 = 2100 RPM (70 Hz)
3 = 2400 RPM (80 Hz)
4 = 2700 RPM (90 Hz)
5 = 3000 RPM (100 Hz)
6 = 3300 RPM (110 Hz)
7 = 3600 RPM (120 Hz)

Accel/Decel Switch

Max Speed Switch

(See section 8.1)

(See section 8.2)

(SW2)

(SW1)

Minimum Speed From Terminal Block Inputs

Reverse Disabled (Reverse Lockout)

Ramp-to-Rest Stop

= Default Setting (Off Position)

0 Hz Minimum Speed

Reverse Enabled

Coast-to-Rest Stop

8

67

Analog Speed Reference From Terminal Block

Constant Torque Curve

Auto Restart Enabled

Power-Up Start Enabled

Relay Control Output: Faulted

1> Speed Reference From Operator Controls

Relay Control Output: Running

Power-Up Start Disabled

Variable Torque Curve

Auto Restart Disabled

45

3

2

N

1

O

91

0

Start from Terminal Block

Parameter Settings from EEPROM Memory

0 = 1 sec accel / 5 sec decel
1 = 5 sec (Default)
2 = 10 sec
3 = 15 sec
4 = 20 sec
5 = 30 sec
6 = 60 sec
7 = 90 sec

2

6

3

4

5

1

0

7

1> Switches 2 and 9 apply to local operator control units only.

Setup Slide Switch

(SW3)

(See section 8.3)

1> Start from Operator Controls

2> Parameter Settings from Setup Switches

2> Switch 10 is used with the DeviceNet Communication option only.