Transfer applications to a PanelView Plus terminal

16-5

• •

If you are using a serial connection for the transfer, specify and set up the driver.

You can also transfer applications to the terminal using a Flash Card. For information
about this method, see the PanelView Plus Terminals User Manual.

To specify and set up a serial driver for the transfer

1. In the FactoryTalk View ME Station dialog box, click Terminal Settings.

2. Double-click Networks and Communications.

3. In the Networks and Communications dialog box, double-click RSLinx Enterprise

Communications.

4. Click the Serial-DF1 driver, and then click Edit Driver.

5. Select Use Auto-Configuration, and then click Edit.

6. In the dialog box that opens, select Yes, and then click OK.

Auto configuration works with most devices, including Logix5000 and PLC-5. If auto
configuration is not successful for your device, return to these steps, select No, and
continue to step 7.

7. Set up the driver, and then click OK. If you are using auto configuration, skip this

step.