FactoryTalk Alarms and Events has been tested to conform to the following
performance limits.

Controller specifications

Execution times for alarms

Scan times increase more during a scan when many alarms change state at the same
time.

An alarm state change is any event that changes the condition of the alarm. To
minimize the potential for large alarm bursts, create dependencies on related alarms.
Large alarm bursts can have a significant impact on the scan time of application code.

Specification

Value

Number of subscribers (RSLinx
Enterprise servers) per controller

16

Controller memory used for buffering by
each subscriber (RSLinx Enterprise)

100KB

Typical number of alarm state transitions
per subscriber

1000

Recommended maximum number of
alarms per controller

2000

Approximate controller memory used for
each alarm

Digital 1 KB; Analog 2.2 KB; Using
associated tags, string tags consume 750-
1600 bytes per string tag depending on
the alarm type.

Supported languages for alarm messages

All languages supported by FactoryTalk
View.

Rung State

Execution times

ALMD instruction

ALMA instruction

False with no alarm state
change

8 μs

17

µs

False with alarm state change

35 µs

17 µs

True with no alarm state
change

8 µs

65 µs

True with alarm state change

35 µs

126 µs