3

Define device-based alarms in Logix5000 controllers

• •
• •

41

Step 5: Add a JSR instruction to the MainRoutine to run the function block:

1. Double-click MainRoutine to open it.

2. Right-click the first rung and then click Add Ladder Element on the context

menu.

3. In the Add Ladder Element dialog box, scroll down to the Program Control

folder and then double-click the folder to expand the list of controls.

4. Select JSR and then click OK.

5. In the JSR instruction, double-click Routine Name and then click alarm_active in

the list.

6. On the toolbar, click the Save button to save the configuration.