FactoryTalk Alarms and Events System Configuration Guide

16

• •

• •

Decide what type of alarm monitoring you need

FactoryTalk Alarms and Events supports two types of alarm monitoring:

„

Device-based alarm monitoring

. Built-in alarm instructions, that are available in

RSLogix 5000 v. 16 or later, are programmed in a logic project and then
downloaded to a Logix5000 controller. The controller detects alarm conditions
and publishes event information, which can be displayed and logged.

„

Tag-based alarm monitoring

. Software-based tag alarm and event servers

monitor controllers for alarm conditions through data servers and publish event
information, which can be displayed and logged. Tag-based alarm monitoring is
supported for Logix5000, PLC-5, and SLC 500 devices communicating through
Rockwell Automation device servers (RSLinx Enterprise), or for third-party
controllers that communicate through OPC Data Servers.

You can use a mix of both types of alarm monitoring. Choose tag-based alarm
monitoring if you do not want to change the logic in your programmable controllers.
Choose tag-based alarm monitoring, if you do not want to update the firmware in
Logix5000 controllers.

What you need

„

Decide what type of application you are building.

„

Decide what type of alarm monitoring you need.

„

Install and activate FactoryTalk software.

„

Update Logix5000 firmware to version 16 if you plan to use device-based alarm
monitoring and alarm instructions that are built into Logix5000 controllers. If you
do not plan to use device-based alarm instructions, you can skip this step and use
tag-based alarm monitoring with a Tag Alarm and Event Server instead.