FactoryTalk Alarms and Events System Configuration Guide

176

• •

• •

Tested system limits

For historical alarm logging, you must be able to log on to a Microsoft SQL Server
2005 Express (SP2), SQL Server 2000 (SP4), or SQL Server 2005 database.

When a controller becomes disconnected from alarm servers on the network, it might
take several minutes to reconnect, depending on the number of controllers and alarms
in the system.

Tested limit

Value

Number of alarms per FactoryTalk
application

20,000

Number of Rockwell Automation Device
Servers per application

2

Number of alarms per Rockwell
Automation Device Server (RSLinx
Enterprise)

10,000

Number of Tag Alarm and Event Servers
per application

2

Number of alarms per Tag Alarm and
Event Server

10,000

Alarm burst (number of alarms occurring
at once)

2000

Simultaneous alarm operations (for
example, enabling, disabling,
acknowledging, or suppressing alarms)

2000

Number of alarms the alarm summary
can display at once

2000

Number of clients simultaneously
connected to the application

20