117

Troubleshooting

Appendix C

6. Issue the command that you feel is failing to execute, such as the Jog Forward command on

the HMI screen. Press and hold this button while you perform step 7…step 8 including
resulting steps
.

7. Observe rung 2 of the R04_Commands_MANUAL routine and carefully note what value is in

the ManualCycle.StepIndex register.

8. Use the table below to determine where the cycle is stopping and what action to take next.

Correct Manual Cycle Problem: Reset Command Is Not Commanding Any Action

The reset command is not commanding any action. Perform the following steps to correct this
condition.

1. Observe the logic on rung 5 of the R04_Commands_MANUAL routine.

2. Verify that one of the manual actions is being requested on this rung from the HMI. (Note that

the ManualCycle.STOPPED tag may not be active if the reset has been commanded.)

If ManualCycle.StepIndex =

The current
state is:

Take this action:

0

Stopped

Go to

Correct Manual Cycle Problem: Reset Command Is Not Commanding Any Action

.

10

Resetting

Go to

Correct Manual Cycle Problem: ManualCycle.StepIndex Stops at 10

.

20

Resetting

Go to

Correct Manual Cycle Problem: ManualCycle.StepIndex Stops at 20

200

Running

Go to

Correct Manual Cycle Problem: ManualCycle.StepIndex Stops at 200

.