Publication IASIMP-QS011B-EN-P — January 2009

Chapter 5

Motion Logix Integration

7. Double-click the drive symbol in the On-Line section to

view its current settings.

You may wish to click Reset EEPROM to Factory Settings if you are not sure what parameters
have been previously changed in the drive.

8. Carefully use the pull-down menu to select the

proper Motor Model from the list.

9. Expand the drive’s Explorer window by clicking the ‘+’ sign

next to the drive symbol.

10. Double-click the DeviceNet folder.

11. Select Assembly Instance 9 for the I/O Receive

Select entry.

12. Set the Poll Transmit Select to Assembly

Instance 12.

13. Verify that the COS/Cyclic Transmit Select

is set to Assembly Instance 10.

These settings allow us to get the most data and diagnostics out of the drive.

IMPORTANT

Verify that you removed the ‘Enable’ input in the steps above. The drive may enable and
run if the Enable signal is present.