4 component locations – Rockwell Automation SP500  AC Drive Installation and Operation Manual User Manual

Page 22

Advertising
background image

2-8

SP500 AC Drive Installation and Operation Manual Version 3.1

Table 2.2 - Power and NEMA Enclosure Ratings (Continued)

*

To properly size the drive for motor nameplate horsepower and amps, refer to section 3.5 for more information. Derating for 4, 6, 8kHz
carrier frequencies is not required except for the units indicated.

**

Refer to section 2.3.2 for more information on enclosure sizes.

*** Full-load at all carrier frequencies. Refer to section 3.1.3 for more information.

2.3.2 Enclosure Ratings and Sizes

Each of the SP500 drives have one of the following NEMA ratings:

See table 2.2 for a listing of drive model numbers and their individual NEMA ratings.

For clarity in this manual, SP500 drive enclosures are identified by size as enclosures
A through D. Refer to table 2.2 for a listing of the drive model numbers and their
individual enclosure sizes. Refer to section 3.1.1 for the dimensions of enclosures A
through D.

2.4

Component Locations

Figures 2.5 through 2.8 show the main components of the SP500 drives (enclosures A
through D). Appendix F lists replacement parts.

Model

Number

Input Power

and Horsepower

Rating*

NEMA

Rating

Enclosure

Size**

AC Input

Volts

Input

Amps

Input

KVA

Output

Amps*

Power

Loss

Watts***

1SU51002

Three-Phase - 2 HP

1

B

575

3.4

3.3

2.7

90

1SU54002

Three-Phase - 2 HP

4X/12

B

575

3.4

3.3

2.7

90

1SU51003

Three-Phase - 3 HP

1

B

575

5.2

5.1

4.3

120

1SU54003

Three-Phase - 3 HP

4X/12

B

575

5.2

5.1

4.3

120

1SU51005

Three-Phase - 5 HP

1

B

575

7.5

7.5

6.2

150

1SU54005

Three-Phase - 5 HP

4X/12

B

575

7.5

7.5

6.2

150

1SU51007

Three-Phase - 7.5 HP

1

C

575

10.9

10.9

9.0

180

1SU54007

Three-Phase - 7.5 HP

4X/12

C

575

10.9

10.9

9.0

180

1SU51010

Three-Phase - 10 HP

1

C

575

14.5

14.4

12.0

250

1SU54010

Three-Phase - 10 HP

4X/12

C

575

14.5

14.4

12.0

250

NEMA

Rating

Description

1

Vented. For general-purpose indoor applications.

4X/12

Not vented. Supplied with base and keypad gaskets. For use in indoor
environments that require a water-tight and dust-tight enclosure. An
enclosure with this NEMA rating encompasses both ratings (4X and 12).

12

Intended for use in indoor environments that require a dust-tight and
drip-tight enclosure.

Advertising