3 selecting input ac line branch circuit fuses – Rockwell Automation SP500  AC Drive Installation and Operation Manual User Manual

Page 36

Advertising
background image

3-8

SP500 AC Drive Installation and Operation Manual Version 3.1

3.3

Selecting Input AC Line Branch Circuit Fuses

Input line branch circuit protection fuses must be used to protect the input power lines.
See figure 5.1. Table 3.9 shows recommended fuse values. These fuse ratings are
applicable for one drive per branch circuit. No other load may be applied to that fused
circuit. Note that contactors and circuit breakers are not recommended for AC input
line branch protection.

* Recommended fuse type: UL Class J, 600V, time-delay, or equivalent.

!

ATTENTION: Most codes require that upstream branch circuit protection
be provided to protect input power wiring. Install the fuses recommended
in table 3.9. Do not exceed the fuse ratings.

Table 3.9 – AC Input Line Fuse Selection Values

Model

Number

Fuse

Rating*

Model

Number

Fuse

Rating*

Model

Number

Fuse

Rating*

1SU11001

20A

1SU41001

6A

1SU51001

4A

1SU14001

12A

1SU44001

6A

1SU54001

4A

1SU41002

8A

1SU51002

7A

1SU21001

10A

1SU44002

8A

1SU54002

7A

1SU24001

10A

1SU41003

12A

1SU51003

10A

1SU21002

30A

1SU44003

12A

1SU54003

10A

1SU41005

25A

1SU51005

15A

1SU21001

12A

1SU44005

25A

1SU54005

15A

1SU24001

12A

1SU41007

25A

1SU51007

20A

1SU21002

20A

1SU44007

25A

1SU54007

20A

1SU24002

20A

1SU41010

35A

1SU51010

25A

1SU21003

25A

1SU44010

35A

1SU54010

25A

1SU24003

25A

1SU41015

45A

1SU21005

35A

1SU42015

45A

1SU24005

35A

1SU41020

55A

1SU42020

55A