Technical Specifications

A-1

A

PPENDIX

A

Technical Specifications

Table A.1 – Service Conditions

AC Line Distribution Capacity
(Maximum)

100KVA, single-phase 115VAC and three-phase 230VAC, with 5,000 amps
symmetrical fault current capacity for M/N 1SU1xxxx and1SU2xxxx drives

1000KVA, three-phase 460 and 575VAC, with 30,000amps symmetrical fault
current capacity for M/N 1SU4xxxx and 1SU5xxxx drives

Control Method

All-digital, pulse-width-modulated (PWM)

Carrier Frequency

4 kHz, 6 kHz, or 8 kHz, software selectable

Displacement Power Factor

0.96

Line Frequency

50/60 Hz (± 5 Hz)

Line Voltage Variation

–10% to +10%

Line Dip RideThrough

500 milliseconds

Linearity

0.05 (Speed reference to output frequency)

Long-term Frequency Stability 0.01%

Minimum Frequency Range

0.5 – 30 Hz

Maximum Frequency Range

30 – 240 Hz

Maximum Load

150% for 1 minute (nominal, based on drive nameplate rating)

Motor Lead Lengths

76 meters (250 feet) total (See table 3.7 for more information)

Overcurrent Trip IET

200% rated drive current

Table A.2 – Dimensions

Enclosure

Height

Depth

Width

Weight

A

304.8mm (12.00”)

121.9mm (4.80”)

146.0mm (5.75”)

2.7 kg (6 lb)

B

301.7mm (11.88”)

160.1mm (6.30”)

222.3mm (8.75”)

5.4 kg (12 lb)

C

357.8mm (14.10”)

158.2 mm (6.20”)

278.1mm (10.9”)

8.1 kg (18 lb)

D

465.2mm (18.31”)

198.9mm (7.83”)

286.5mm (11.28”)

15.3 kg (34 lb)

Table A.3 – Environmental Conditions

Operating Temperature

0° to +40°C (32° to 104°F) – enclosed drives
0° to +55°C (32° to 131°F) – open chassis (cover removed)

Storage Temperature

– 40° to +65°C (– 40° to +149°F)

Humidity

5 to 95% (non-condensing)

Altitude

Do not install the drive above 1000 meters (3300 feet) without derating
output power. For every 91.4 meters (300 feet) above 1000 meters
(3300 feet) up to 3033 meters (10,000 feet), derate the output current by
1%. Above 3033 meters (10,000 feet), contact your local Reliance
Electric sales office for assistance.