3 output power wiring – Rockwell Automation SP500  AC Drive Installation and Operation Manual User Manual

Page 58

Advertising
background image

5-10

SP500 AC Drive Installation and Operation Manual Version 3.1

5.2.5 Output Status Relay Wiring

Output status wiring connects to terminals 14 through 16 on the Regulator board’s
terminal strip. See figure 5.11. Parameter F-09 specifies the type of status indication
provided by the output relay. See the F-09 parameter description in section 8.3 for
more information.

5.3

Output Power Wiring

Use the following steps to connect AC output power wiring from the drive to the motor:

Step 1. Wire the AC output power leads by routing them according to the type of

enclosure. See figures 4.1 through 4.4. See tables 3.2 through 3.4 for
recommended wire sizes.

.

Do not route more than three sets of motor leads through a single conduit. This will
minimize cross-talk which could reduce the effectiveness of noise reduction methods.
If more than three drive/motor connections per conduit are required, you must use
shielded cable. If possible, each conduit should contain only one set of motor leads.

Step 2. Connect the AC output power motor leads to terminals U, V, and W on the

power terminal strip. See figure 5.1.

Step 3. Tighten terminals U, V, and W to the proper torque as shown in table 3.5.

Figure 5.11 – Output Status Relay Wiring Connections

14

15 16

N.O.

USER-SUPPLIED

LAMP

USER-SUPPLIED
115 VAC / 24 VDC
(10 mA Min.)

!

ATTENTION: Do not route signal and control wiring with power wiring
in the same conduit. This can cause interference with drive operation.

!

ATTENTION: Unused wires in conduit must be grounded at both ends
to avoid a possible shock hazard caused by induced voltages. Also, if
a drive sharing a conduit is being serviced or installed, all drives using
this conduit should be disabled to eliminate the possible shock hazard
from cross-coupled motor leads.

Advertising