Chapter 8 programming reference, Hapter, Programming reference – Rockwell Automation SP500 AC Drive Installation and Operation Manual User Manual
Page 73: 1 displaying or changing parameter values

Programming Reference
8-1
C
HAPTER
8
Programming Reference
To program the SP500 drive for a specific application, you display the appropriate
parameter and adjust it as required. The parameters specify characteristics of the
drive. This chapter describes how to access, display, and modify parameters. Section
8.3 describes each parameter in detail. Appendix C lists the parameters in
alphabetical order.
8.1
Displaying or Changing Parameter Values
Use the following procedure to display or change parameter values:
Step 1. Stop the drive (if it is running) by pressing the STOP/RESET key.
Step 2. Enter program mode by pressing the MODE/ENTER key until the
PROGRAM LED turns on.
The first parameter number (F-00) will be
displayed.
Step 3. Press the
or
key until the desired parameter number is
displayed.
Each parameter number will be displayed as
you scroll through the parameter list.