2 analog output wiring, 3 digital input wiring – Rockwell Automation SP500  AC Drive Installation and Operation Manual User Manual

Page 52

Advertising
background image

5-4

SP500 AC Drive Installation and Operation Manual Version 3.1

5.2.2 Analog Output Wiring

Analog output wiring connects to terminals 4 and 5 on the Regulator board’s terminal
strip. See figure 5.4. This is a scaled 0 to 10 VDC output signal that is proportional to
either current speed, percent of load, calculated output voltage, or percent of the
selected reference value, whichever is selected through parameter F-29. This output
signal is available during both local and remote operation.

5.2.3 Digital Input Wiring

Digital input wiring connects to terminals 6 through 11 on the Regulator board’s
terminal strip. The drive has a 24 VDC power supply that provides the required voltage
for control signals. Enabling or disabling a control signal requires that a contact
(switch) be opened or closed.

Important: The 24 VDC power supply is unregulated and will nominally supply

24 VDC. It is not to be used with any external devices other than the
inputs to the drive.

Figure 5.3 – Analog Speed Reference Wiring Connections

5k

+10 VDC

User-Supplied

Speed Reference

Potentiometer

0-10 VDC

or

0-20 mA

User-Supplied

Speed Reference

Input Signal

or

Figure 5.4 – Analog Output Wiring Connections

+10V 0V

Load

(User-Supplied

Analog Meter)

Advertising