2 ensuring program security – Rockwell Automation SP500 AC Drive Installation and Operation Manual User Manual
Page 75

Programming Reference
8-3
8.2
Ensuring Program Security
Parameter values can be password-protected using parameter F-20 (Password
Lockout Enable). When F-20 is set to ON, parameter values can be displayed but
cannot be modified from the keypad unless the correct password is entered in F-20.
Important: The password is factory set to 257 and cannot be modified by the user.
Use the following procedure to disable or enable parameter programming:
!
ATTENTION: It is the user’s responsibility to determine how to distribute
the password. Reliance Electric is not responsible for unauthorized
access violations within the user’s organization.
Step 1. In program mode, press the
or
key until F-20 is displayed.
Step 2. Press the MODE/ENTER key to access the parameter. ON or OFF is
displayed to indicate whether the password lockout feature is currently
enabled or disabled.
Program Enabled
Program Disabled