4-8

SP500 AC Drive Installation and Operation Manual Version 3.1

Use the following procedure to set jumper J6:

Step 1. Turn off and lock out input power. Wait five minutes.

Step 2. Remove the cover from the drive by unscrewing the four cover screws.

Step 3. Verify that the DC bus voltage is zero by following the procedure in section

9.1.

Step 4. Locate jumper J6 on the Regulator board. Refer to figure 2.3.

Step 5. Move the jumper to the desired setting as shown in figure 4.5.

Step 6. Reattach the cover.

Step 7. Reapply input power.

Step 8. Verify that parameters F-11 and F-12 are correctly set.

Note that if the setting of jumper J6 is changed, the regulator software will not
automatically detect it. Verify that parameters F-11 (gain) and F-12 (offset) are set
correctly before starting the drive.

4.5

Preparing the Motor

Follow these guidelines when preparing to install the motor:

Verify that the motor is the appropriate size to use with the drive.

Verify that the total motor lead length does not exceed the values given in section
3.2.4.

Follow the instructions in the motor instruction manual when installing the motor.

Figure 4.5 – Jumper J6 Settings for the Analog Input Speed Reference

!

ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait five
(5) minutes for the DC bus capacitors to discharge and then check the
voltage with a voltmeter to ensure the DC bus capacitors are discharged
before touching any internal components.

J6

1

2

3

4

16

5

6

7

8

9 10 11

12 13 14

15

0-20 mA

0-10 VDC