9-8

SP500 AC Drive Installation and Operation Manual Version 3.1

.

* (+) DC bus volts power terminal
** (–) DC bus volts power terminal

* (+) DC bus volts power terminal
** (–) DC bus volts power terminal

Table 9.2 – Resistance Checks for Input Diodes

Input

Diode

No.

Meter

Connection

Component is OK if

resistance (R) is:

Component is

defective if:

(+)

(-)

1

*

R/L1

50 < R < 10 Megohm

Continuity (short circuit) or
open when the meter is
connected with reversed
polarity.

2

*

S/L2

3

*

T/L3

4

R/L1

**

5

S/L2

**

6

T/L3

**

Table 9.3 – Resistance Checks for IGBTs

IGBT

No.

Meter

Connection

Component is OK if

resistance (R) is:

Component is

defective if:

(+)

(–)

1

*

W/T3

50 < R < 10 Megohm

Continuity (short circuit) or
open when the meter is
connected with reversed
polarity.

2

*

V/T2

3

*

U/T1

4

W/T3

**

5

V/T2

**

6

U/T1

**