Rockwell Automation SP500 AC Drive Installation and Operation Manual User Manual
Page 98
![background image](/manuals/581524/98/background.png)
9-8
SP500 AC Drive Installation and Operation Manual Version 3.1
.
* (+) DC bus volts power terminal
** (–) DC bus volts power terminal
* (+) DC bus volts power terminal
** (–) DC bus volts power terminal
Table 9.2 – Resistance Checks for Input Diodes
Input
Diode
No.
Meter
Connection
Component is OK if
resistance (R) is:
Component is
defective if:
(+)
(-)
1
*
R/L1
50 < R < 10 Megohm
Continuity (short circuit) or
open when the meter is
connected with reversed
polarity.
2
*
S/L2
3
*
T/L3
4
R/L1
**
5
S/L2
**
6
T/L3
**
Table 9.3 – Resistance Checks for IGBTs
IGBT
No.
Meter
Connection
Component is OK if
resistance (R) is:
Component is
defective if:
(+)
(–)
1
*
W/T3
50 < R < 10 Megohm
Continuity (short circuit) or
open when the meter is
connected with reversed
polarity.
2
*
V/T2
3
*
U/T1
4
W/T3
**
5
V/T2
**
6
U/T1
**