Programming Reference

8-15

F-22 Avoidance Bandwidth

(continued)

Setting F-00 = 3 (multi-speed configuration) reconfigures the terminal strip control
inputs as follows:

Terminal 6 = START/STOP/IET RESET (open = STOP; closed = IET RESET/START)
Terminal 7 = MSPD 1
Terminal 8 = MSPD 0

Refer to section 5.2.

Terminals 7 and 8 are used to select the reference source as shown in table 8.1.

Example

Assume:

Minimum Speed (F-03) = 3 Hz
Maximum Speed (F-04) = 60.0 Hz
Avoidance Frequency (F-21) = 32.2 Hz
Avoidance Bandwidth (F-22) = 4 Hz
Avoidance Band = 30.2 to 34.2 Hz

Requested Output

Frequency

Output Frequency After

Avoidance Band Correction

25.0 Hz

25.0 Hz

30.0 Hz

30.0 Hz

31.0 Hz

30.2 Hz

32.0 Hz

30.2 Hz

34.0 Hz

30.2 Hz

34.2 Hz

30.2 Hz

34.3 Hz

34.3 Hz

35.0 Hz

35.0 Hz

F-23, F-24, and F-25 Multi-Speed Presets 1, 2, and 3

These parameters
allow the setting of up
to three different
preset speeds.

Parameter Range:

Default Setting:

Step Size:

Minimum speed to maximum speed

20 Hz

0.10 Hz

Table 8.1 – Multi-Speed Presets Digital Inputs

MSPD 1

MSPD 0

Reference Source

Open (0)

Open (0)

Terminal strip analog input (variable speed)

Open (0)

Closed (1)

Multi-Speed #1 (F-23)

Closed (1)

Open (0)

Multi-Speed #2 (F-24)

Closed (1)

Closed (1)

Multi-Speed #3 (F-25)