SP500 System Planning

3-7

1. Note that the lead lengths listed are valid with Reliance Electric inverter duty motors.
2. N/A indicates that the drive does not have this rating or it is not applicable.

.

1. MTE standard reactors can be used on SP500 drives with carrier frequency settings up to 8 kHz.
2. All reactors listed are UL-recognized (UL-506 File #E53094) and CSA certified (CSA File #LR29753).

Table 3.7 – Motor Lead Lengths

SP500 HP

Rating

Filter Type

Maximum Lead

Length in Feet with

230 VAC Motor

Maximum Lead

Length in Feet with

460 VAC Motor

Maximum Lead

Length in Feet with

575 VAC Motor

Carrier Frequency

Carrier Frequency

Carrier Frequency

4 kHz

6 kHz

8 kHz

4 kHz

6 kHz

8 kHz

4 kHz

6 kHz

8 kHz

1

None

500

500

500

250

250

250

150

150

150

2

500

500

500

350

350

350

250

200

200

3

1000

1000

1000

400

400

400

250

200

200

5

1000

1000

1000

500

500

500

250

200

200

7.5 to 10

N/A

N/A

N/A

500

500

500

250

250

250

15 to 20

N/A

N/A

N/A

500

500

500

N/A

N/A

N/A

1

A 5% MTE

reactor/filter at the

drive.

A reactor/filter is not

required. Above lead

lengths are maximum

distances.

500

500

500

500

500

500

2

500

500

500

500

500

500

3

1000

1000

1000

1000

1000

1000

5

1000

1000

1000

1000

1000

1000

7.5 to 10

N/A

N/A

N/A

1000

1000

1000

1000

1000

1000

15 to 20

N/A

N/A

N/A

1000

1000

1000

N/A

N/A

N/A

Table 3.8 – Reactors

SP500 HP Rating

230 Volt

5% MTE Reactor

480 Volt

5% MTE Reactor

600 Volt

5% MTE Reactor

1

RL-00402

RL-00202

RL-00203

2

RL-00403

RL-00404

3

RL-00403

RL-00404

5

RL-00803

RL-00804

7.5

RL-01203

RL-00803

10

RL-01803

RL-01203

15

RL-02503

20

RL-03503

Advertising