Advertising
background image

SP500 System Planning

3-5

.

*Except for M/N 1SU21002 (single-phase input), 1SU21005, and 1SU24005, for which 12 AWG, 3 (mm

2

)

wire is recommended.

* Except for M/N 1SU41010 and 1SU44010, for which 12 AWG, 3 (mm

2

) wire is recommended.

Table 3.2 – Recommended Power Wire Sizes for M/N 1SU1xxxx and 1SU2xxxx Drives

Type of Wiring

Terminals

Size of Wire
(maximum)*

AC Input Power

R, S, T

14 AWG, 2 (mm

2

)

Output Power

U, V, W

14 AWG, 2 (mm

2

)

DC Bus

– , +

14 AWG, 2 (mm

2

)

Ground

GND

14 AWG, 2 (mm

2

)

Table 3.3 – Recommended Power Wire Sizes for M/N 1SU4xxxx and 1SU5xxxx Drives

Type of Wiring

Terminals

Size of Wire
(maximum)*

AC Input Power

R(L1), S(L2), T(L3)

14 AWG, 2 (mm

2

)

Output Power

U(T1), V(T2), W(T3)

14 AWG, 2 (mm

2

)

DC Bus

– , +

14 AWG, 2 (mm

2

)

Snubber Resistor

+10 VDC, 10 COM

14 AWG, 2 (mm

2

)

Ground

GND

14 AWG, 2 (mm

2

)

Table 3.4 – Recommended Power Wire Sizes for M/N 1SU4x015 and 1SU4x020 Drives

Type of Wiring

Terminals

Size of Wire

(maximum)

AC Input Power

R/L1, S/L2, T/L3

12 AWG, 3 (mm

2

)

Output Power

U/T1, V/T2, W/T3

12 AWG, 3 (mm

2

)

DC Bus

– , +

12 AWG, 3 (mm

2

)

Snubber Resistor

–, +

12 AWG, 3 (mm

2

)

Ground

GND

12 AWG, 3 (mm

2

)

Table 3.5 – Recommended Power Terminal Tightening Torque

Drives

Terminals

Maximum Tightening Torque

All

All power wires

1.08 Newton-meters (9.5 in-lb)