Chapter 5 wiring the drive, Hapter, Wiring the drive – Rockwell Automation SP500 AC Drive Installation and Operation Manual User Manual
Page 49

Wiring the Drive
5-1
C
HAPTER
5
Wiring the Drive
This chapter describes how to wire the SP500 drive including: input wiring, control and
signal wiring, output wiring, and grounding.
5.1
Input Power Wiring
Use the following steps to connect AC input power to the drive:
Step 1. Verify that the AC input power to the drive corresponds to the drive’s
nameplate voltage and frequency.
Step 2. Wire the AC input power leads by routing them according to the type of
enclosure. See figures 4.1 through 4.4. See tables 3.2 through 3.4 for
recommended wire sizes.
.
Step 3. Connect the AC input power leads to terminals R,S,T on the power terminal
strip. See figure 5.1.
Step 4. Tighten terminals R and S (single-phase input) or terminals R,S,T (three-
phase input) to the proper torque as shown in table 3.5.
!
ATTENTION: Do not route signal and control wiring with power wiring in
the same conduit.This can cause interference with drive operation.