6 drive control – Rockwell Automation SP500  AC Drive Installation and Operation Manual User Manual

Page 70

Advertising
background image

7-6

SP500 AC Drive Installation and Operation Manual Version 3.1

A sample monitor mode display is shown in figure 7.4.

7.5.1 Displaying the Percent Selected Speed Reference

To display the percent selected speed reference, parameter F-13 must be set to ON.
Use the following procedure to display the percent selected speed reference:

Step 1. Stop the drive (if it is running) by pressing the STOP/RESET key.

Step 2. Enter program mode by pressing the MODE/ENTER key until the PROGRAM

LED turns on.

Step 3. Press the

or

key until F-13 is displayed.

Step 4. Press the MODE/ENTER key to access the parameter.

Step 5. Press the

key until ON is displayed.

Step 6. Press the MODE/ENTER key to save the value. (F-13 will be displayed.)

Step 7. Press the STOP/REST key to exit program mode.

Step 8. Start the drive by pressing the START key.

Step 9. Press the MODE/ENTER key until all three monitor mode LEDs are on.

The display will show the active speed reference as 1 to 100% of maximum speed
(F-04).

7.5.2 Scaling the RPM Display and Reference Using F-08

The RPM display and reference can be scaled to an engineering unit to match your
application. Refer to the F-08 description in chapter 8 for this procedure.

7.6

Drive Control

When the control source is the local keypad (F-00 = 0), the keypad is used to control
the drive. This means that the drive will respond to START, STOP/RESET, and
FORWARD/REVERSE commands only from the keypad.

Figure 7.4 – Example of a Monitor Mode Display

Mode

Enter

START

Forward
Reverse

STOP

RESET

RPM

%Load

Volts

Remote

RUN
Program

Forward
Reverse