Motor namepl rpm (u.005), Motor namepl hp (u.022) – Rockwell Automation GV3000/SE Operator Interface Module (OIM) User Guide User Manual
Page 50
 
5-10
GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0
In V/Hz regulation, this parameter configures the V/Hz ratio. Base frequency is the 
frequency at which the output voltage reaches MOTOR NAMEPL VOLTS (H.000). 
Below base frequency, the output voltage varies with output frequency according to 
the V/Hz adjustment in VHZ-CURVE TYPE (H.018). Above base frequency, output 
voltage is held constant as frequency increases (constant horsepower range).
The V/Hz ratio is affected by the selection of VHZ-CURVE TYPE (H.018) and the 
setting of TORQUE BOOST VOLTAGE (H.003).
*The actual range of this parameter is based on the values of MOTOR POLES (U.002) 
and MOTOR NAMEPL BASE FRQ (U.003). See the software I/M for calculations.
If the value of this parameter is too close to the synchronous RPM, the drive might be 
unstable. This value directly affects torque linearity and the maximum attainable 
horsepower.
MOTOR NAMEPL BASE FRQ (H.001 or U.003)
In vector regulation, 
this parameter 
identifies the motor 
base frequency as it 
appears on the motor 
nameplate.
Parameter Range:
15.0 to 240.0 HERTZ (vector)
30.0 to 200.0 HERTZ (V/Hz)
Default Setting:
60.0 HERTZ
Parameter Type:
Configurable
!
ATTENTION: The setting of parameters U.001 (Encoder PPR), U.002 
(Motor Poles), U.003 (Motor Nameplate Base Frequency), and U.005 
(Motor Nameplate RPM) determins the motor manximum speed. These 
parameters must be set by a qualitifed person who understands the 
significance of setting them accurately. Failure to observe this 
precaution could result in bodily injury.
MOTOR NAMEPL RPM (U.005)
Indentifies the motor 
rated RPM as it 
appears on the motor 
nameplate. 
.
Parameter Range:
675 to 3596*
Default Setting:
Power Module-dependent. See the software I/M for 
more information.
Parameter Type:
Configurable
MOTOR NAMEPL HP (U.022)
Identifies the motor 
horsepower as it 
appears on the motor 
nameplate.
Parameter Range:
0.3 to 600.0 HP
Default Setting:
Power Module-dependent. See the software I/M for 
more information
Parameter Type:
Configurable