Accel time (p.001) – Rockwell Automation GV3000/SE Operator Interface Module (OIM) User Guide User Manual
Page 51
 
Using Quick Start to Program the Drive
5-11
The time the motor takes to increase speed is directly proportional to the value in this 
parameter. This parameter does not apply to jog.
If the motor load inertia is high, or the CURRENT LIMIT (P.005) setting is too low, 
actual motor acceleration time will be longer than the time set in ACCEL TIME. If 
ACCEL TIME is set too short, an overcurrent fault might occur.
MOTOR NAMEPL VOLTS (H.000 or U.007)
Identifies the motor 
rated (nominal) 
voltage as it appears 
on the motor 
nameplate.
Parameter Range:
100 to 690 VOLTS
Default Setting:
460 VOLTS
Parameter Type:
Configurable
MOTOR NAMEPL AMPS (H.002 or U.004)
Identifies the motor 
rated amps as it 
appears on the motor 
nameplate.
Parameter Range:
Power Module-dependent. See the software I/M for
more information.
Default Setting:
Power Module-dependent. See the software I/M for 
more information.
Parameter Type:
Configurable
!
ATTENTION:  This parameter must not exceed the rated amps found 
on the motor nameplate. Overcurrent or excessive heating of the motor 
could result if rated amps are exceeded. Failure to observe this 
precaution could result in damage to, or destruction of, the equipment.
ACCEL TIME (P.001)
Specifies the time it 
takes for the motor to 
increase from zero 
speed to MAXIMUM 
SPEED, P.004 (V/Hz 
regulation), or 
MOTOR TOP 
SPEED, U.017 
(vector regulation).
Parameter Range:
1.0 to 999.9 SEC (V/Hz)
0.1 to 999.9 SEC (vector)
Default Setting:
20.0 SEC
Parameter Type:
Tunable